Correct charging method of lithium iron phosphate battery.

Web:www.topbandbattery.com     Date:2022-12-05

It is recommended to use CCCV charging mode with fixed current and then voltage for charging lithium iron phosphate battery. A constant current of 0.3 C is recommended. The constant voltage is 3.65, that is, the battery is charged at 0.3 C under the constant current state. When the battery voltage reaches 3.65 V, the battery is charged at 3.65 V, and the charging is stopped when the charging current is less than 0.1 C (or 0.05 C). When using a constant voltage power supply, pay attention to the charging current. It is better not to use excessive voltage. After adjustment, keep the charging current within 0.5 C.



The upper limit of charging voltage of lithium iron phosphate battery is 3.7-4 V, and the lower limit of discharge voltage is 2-2.5 V. Considering the discharge capacity, median voltage, charging time, capacity percentage and safety, constant current and constant voltage charging mode is adopted. The charging limit voltage is set as 3.55-3.70 V, the recommended value is 3.60-3.65 V, and the lower limit of discharge voltage is 2.2-2.5 V.



The charging mode of lithium iron phosphate battery is very different from that of ordinary lithium battery. The final charging voltage of lithium battery is 4.2 volts; The lithium iron phosphate battery has a capacity of 3.65 volts. When charging the battery, the lithium iron phosphate battery will first connect the connecting wires of the battery, and then connect the two ends of the battery, so that the battery voltage will be higher than the battery voltage. At the same time, the voltage of a single cell is measured, which is equivalent to a parallel voltage stabilizing tube, so that the charging voltage of a single battery will not exceed the stable range, while other single batteries will continue to be charged in the voltage stabilizing tube.



Since the battery of each battery is almost full, the charging current of the battery is very low, and each battery is fully charged. The charger can only protect the voltage at one end of the battery, and the function of the equalization circuit board is to make each battery of the battery fully charged, rather than one battery being fully charged, which will lead to the interruption of battery charging.


Shenzhen Topband Battery Co., Ltd.,established in 2006, is a wholly-owned subsidiary of Shenzhen Topband Co., Ltd. (002139.SZ). We focus on lithium iron phosphate batteries,with independent research and development in cells and BMS. With the ability to integrate the entire industry chain, we are committed to providing customers with one-stop lithium battery solutions and services. Our quality products are widely used in energy storage and light power.

Related Blog
Why you need the 51.2V 100Ah battery from Topband to support your electricity supply?
Why you need the 51.2V 100Ah battery from Topband to support your electricity supply?
How to Equip the New Energy System for Solar Water Pump?
How to Equip the New Energy System for Solar Water Pump?
Guardian of the Information Age】TOPBAND Battery: The Green Heart of Telecom Base Station Backup Power Storage
Guardian of the Information Age】TOPBAND Battery: The Green Heart of Telecom Base Station Backup Power Storage
The Future of Light Power in a New Era of Energy Storage: Green, Efficient, and Intelligent
The Future of Light Power in a New Era of Energy Storage: Green, Efficient, and Intelligent
About Us
Company Profile R&D Center Manufacturing Honor Company Video Sitemap
Products
Cell Energy Storage Motive Battery
Blog
Company News Events News Industry News
Contact Us
Add:Topband Industrial Park,LiYuan Industrial
Zone,Shiyan,BaoAn District,Shenzhen,China.
Tel:+86-755-2765 1888
E-Mail: support@topbandbattery.com

INQUIRY NOW!